Specifications Table for ATXP-N9 / ARXP-N9

ATXP20N5V1B9 / ARXP20N5V1B9 ATXP25N5V1B9 / ARXP25N5V1B9 ATXP35N5V1B9 / ARXP35N5V1B9
Outdoor unit ARXP20N5V1B9 ARXP25N5V1B9 ARXP35N5V1B9
Cooling capacity Min. kW 1.3 1.3 1.3
  Nom. kW 2.00 2.50 3.50
  Max. kW 2.6 3.0 4.0
Heating capacity Min. kW 1.30 1.30 1.30
  Nom. kW 2.50 3.00 4.00
  Max. kW 3.50 4.00 4.80
Nominal efficiency COP   4.77 4.36 4.02
  EER   3.71 3.71 3.46
  Energy labeling Directive Cooling   A A A
    Heating   A A A
Space cooling Annual energy consumption kWh/a 101 127 178
  Energy efficiency class   A++ A++ A++
  Capacity Pdesign kW 2.00 2.50 3.50
  SEER   6.90 6.90 6.90
Space heating (Average climate) Annual energy consumption kWh/a 663 730 847
  Capacity Pdesign kW 2.20 2.40 2.80
  Energy efficiency class   A++ A++ A++
  Pdh Heating capacity at -10° kW 1.98 2.09 2.32
  SCOP/A   4.64 4.60 4.62
Notes (1) - See separate drawing for electrical data (1) - See separate drawing for electrical data (1) - See separate drawing for electrical data
  (2) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified (2) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified (2) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified
  (3) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (3) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (3) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series