| EWYT085B-SSA1 | EWYT105B-SSA1 | EWYT135B-SSA1 | EWYT175B-SSA1 | EWYT205B-SSA2 | EWYT215B-SSA1 | EWYT235B-SSA2 | EWYT255B-SSA2 | EWYT300B-SSA2-VFDFAN | EWYT300B-SSA2 | EWYT340B-SSA2-VFDFAN | EWYT340B-SSA2 | EWYT390B-SSA2-VFDFAN | EWYT390B-SSA2 | EWYT430B-SSA2-VFDFAN | EWYT430B-SSA2 | EWYT490B-SSA2-VFDFAN | EWYT490B-SSA2 | EWYT540B-SSA2-VFDFAN | EWYT540B-SSA2 | EWYT590B-SSA2-VFDFAN | EWYT590B-SSA2 | EWYT630B-SSA2-VFDFAN | EWYT630B-SSA2 | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Sound pressure level | Cooling | Nom. | dBA | 72 | 74.5 | 75.4 | 75.9 | 76.6 | 76.8 | 77.1 | 77.4 | |||||||||||||||||
| Compressor | Type | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | |||||||||||||||||||
| Starting method | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | ||||||||||||||||||||
| Quantity | 4 | 4 | 4 | 4 | 5 | 6 | 6 | 6 | ||||||||||||||||||||
| Weight | Operation weight | kg | 1,811 | 2,114 | 2,270 | 3,200 | 3,207.27 | 3,397.27 | 4,302.37 | 4,308.08 | ||||||||||||||||||
| Unit | kg | 1,800 | 2,100 | 2,250 | 3,180 | 3,180 | 3,370 | 4,267 | 4,267 | |||||||||||||||||||
| Air heat exchanger | Type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | |||||||||||||||||||
| EER | 2.69 | 2.68 | 2.7 | 2.65 | 2.66 | 2.67 | 2.69 | 2.67 | 2.64 | 2.65 | 2.69 | 2.69 | 2.62 | 2.63 | 2.55 | 2.53 | 2.54 | 2.5 | 2.51 | 2.56 | 2.57 | 2.59 | 2.6 | |||||
| Refrigerant | Type | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | |||||||||||||||||||
| Circuits | Quantity | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||||||||||||||||||
| Charge | kg | 37.2 | 41.7 | 48 | 47.1 | 60.3 | 70 | 78.5 | 87 | |||||||||||||||||||
| Fan motor | Drive | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | |||||||||||||||||||
| Cooling capacity | Nom. | kW | 212 | 270 | 317 | 350 | 434 | 482 | 531 | 570 | ||||||||||||||||||
| IPLV | 4.43 | 4.4 | 4.32 | 4.28 | 4.33 | 4.36 | 4.31 | 4.35 | 4.35 | 4.2 | 4.67 | 4.31 | 4.45 | 4.2 | 4.31 | 4.68 | 4.46 | 4.71 | 4.52 | 4.73 | 4.44 | 4.8 | 4.53 | |||||
| Piping connections | Evaporator water inlet/outlet (OD) | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | |||||||||||||||||||
| SEER | 3.9 | 3.98 | 3.9 | 4.01 | 3.96 | 3.9 | 3.96 | 3.9 | 3.99 | 4.1 | 3.99 | 4 | 4.23 | 4.23 | 4.17 | 4.25 | ||||||||||||
| Power input | Cooling | Nom. | kW | 78.7 | 102 | 117 | 133 | 171 | 192 | 207 | 219 | |||||||||||||||||
| Sound power level | Cooling | Nom. | dBA | 91 | 94 | 94.9 | 95.9 | 96.6 | 96.8 | 97.5 | 97.8 | |||||||||||||||||
| Dimensions | Unit | Width | mm | 1,195 | 2,282 | 2,282 | 2,282 | 2,282 | 2,282 | 2,282 | 2,282 | |||||||||||||||||
| Depth | mm | 4,950 | 3,225 | 3,225 | 4,125 | 4,125 | 4,125 | 5,025 | 5,025 | |||||||||||||||||||
| Height | mm | 1,800 | 2,514 | 2,514 | 2,514 | 2,514 | 2,514 | 2,514 | 2,514 | |||||||||||||||||||
| Capacity control | Minimum capacity | % | 17 | 22 | 19 | 17 | 22 | 19 | 18 | 17 | ||||||||||||||||||
| Method | Step | Step | Step | Step | Step | Step | Step | Step | ||||||||||||||||||||
| Casing | Material | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | |||||||||||||||||||
| Colour | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | ||||||||||||||||||||
| Fan | Type | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | |||||||||||||||||||
| Quantity | 12 | 5 | 6 | 8 | 8 | 8 | 10 | 10 | ||||||||||||||||||||
| Power supply | Phase | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | |||||||||||||||||||
| Voltage range | Max. | % | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | ||||||||||||||||||
| Min. | % | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||||||||||||||||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |||||||||||||||||||
| Voltage | V | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | |||||||||||||||||||
| Unit | Max unit current for wires sizing | A | 201.0 | 255 | 293 | 334 | 417 | 468 | 509 | 542 | ||||||||||||||||||
| Starting current | Max | A | 425.0 | 564 | 598 | 636 | 712 | 757 | 795 | 825 | ||||||||||||||||||
| Running current | Cooling | Nom. | A | 133.0 | 175 | 198 | 228 | 292 | 329 | 354 | 373 | |||||||||||||||||
| Max | A | 183.0 | 232 | 266 | 304 | 379 | 425 | 463 | 493 | |||||||||||||||||||
| Notes | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (1) - All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: 12,0/7,0°C; ambient 35,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | ||||
| (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | (2) - All the performances (Heating capacity, unit power input in heating and COP) are based on the following conditions: 40,0/45,0°C; ambient 7,0°C, unit at full load operation; operating fluid: Water; fouling factor = 0. EN14511:2018 | |||||
| (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | (3) - SCOP is based on the following conditions: Tbivalent -5 °C, Tdesign -10 °C, Average ambient conditions, Ref. EN14825. In accordance with standard EN14825, comfort low temperature, average climate, SEER and µs values applicable Ecodesign regulation: (EU) N | |||||
| (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | (4) - PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter | |||||
| (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | (5) - Sound power (evap. 12/7°C, ambient 35°C full load operation) in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units. Certification refers only to the overall sound power, sound pressure is calculated from sound power level and used for i | |||||
| (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | (6) - The minimum capacity indicated is referred to unit operating at standard Eurovent condition | |||||
| (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | (7) - Dimensions and weights are for indication only and are not considered binding. Before designing the installation, consult the official drawings available from the factory on request. | |||||
| (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | (8) - The data are referred to the unit without additional options. | |||||
| (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | (9) - The values of the Pressure Drops refers to the pressure drops in the Water heat exchanger only. | |||||
| (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | (10) - Fluid: Water | |||||
| (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | (11) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. | |||||
| (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | (12) - Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced. | |||||
| (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | (13) - Nominal current in cooling mode is referred to the following conditions: Water Side Heat Exchanger 12/7°C; ambient 35°C; compressors + fans current | |||||
| (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | (14) - Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current. | |||||
| (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | (15) - Maximum unit current for wires sizing is based on minimum allowed voltage. | |||||
| (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | (16) - Maximum current for wires sizing: (compressors full load ampere + fans current) x 1.1 | |||||
| (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | (17) - For the electrical data of the hydronic kit refer to "Options technical data" part in the data book | |||||
| (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | (18) - All data are subject to change without notice. Please refer to the unit nameplate data. | |||||
| Cooling capacity | Nom. | kW | 75 | 98 | 120 | 153 | 189 | 193 | 230 | 270 | 317 | 350 | 375 | 434 | 482 | 531 | 570 | |||||||||||
| Capacity control | Method | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | Step | ||||||||||||
| Minimum capacity | % | 50 | 38 | 50 | 38 | 19 | 50 | 25 | 22 | 19 | 17 | 25 | 22 | 19 | 18 | 17 | ||||||||||||
| Power input | Cooling | Nom. | kW | 28 | 36.6 | 44.6 | 57.8 | 71.3 | 72.1 | 86.4 | 102 | 117 | 132 | 147 | 171 | 192 | 206 | 219 | ||||||||||
| Dimensions | Unit | Depth | mm | 2225 | 2825 | 3425 | 3425 | 4350 | 4025 | 4950 | 3225 | 3225 | 4125 | 4125 | 4125 | 4125 | 5025 | 5025 | ||||||||||
| Height | mm | 1800 | 1800 | 1800 | 1800 | 1800 | 1800 | 1800 | 2514 | 2514 | 2514 | 2514 | 2514 | 2514 | 2514 | 2514 | ||||||||||||
| Width | mm | 1195 | 1195 | 1195 | 1195 | 1195 | 1195 | 1195 | 2282 | 2282 | 2282 | 2282 | 2282 | 2282 | 2282 | 2282 | ||||||||||||
| Weight | Operation weight | kg | 962 | 1072 | 1172 | 1327 | 1511 | 1511 | 1839 | 2114 | 2270 | 3200 | 3210 | 3207 | 3397 | 4302 | 4308 | |||||||||||
| Unit | kg | 955 | 1065 | 1165 | 1320 | 1500 | 1500 | 1825 | 2100 | 2250 | 3180 | 3190 | 3180 | 3370 | 4267 | 4267 | ||||||||||||
| Casing | Colour | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | Ivory white | ||||||||||||
| Material | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | Galvanized and painted steel sheet | |||||||||||||
| Air heat exchanger | Type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | High efficiency fin and tube type | ||||||||||||
| Fan | Quantity | 4 | 6 | 8 | 8 | 10 | 10 | 12 | 5 | 6 | 8 | 8 | 8 | 8 | 10 | 10 | ||||||||||||
| Type | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | Direct propeller | |||||||||||||
| Fan motor | Drive | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | ON/OFF | ON/OFF | ON/OFF | ON/OFF | ON/OFF | ON/OFF | ON/OFF | ON/OFF | ||||||||||||
| Compressor | Quantity | 2 | 2 | 2 | 2 | 4 | 2 | 4 | 4 | 4 | 4 | 4 | 5 | 6 | 6 | 6 | ||||||||||||
| Type | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | Scroll compressor | |||||||||||||
| Starting method | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | Direct on line | |||||||||||||
| Sound power level | Cooling | Nom. | dBA | 84 | 87 | 89 | 91 | 90 | 92 | 92 | 94 | 95 | 96 | 96.3 | 96.6 | 96.8 | 97.5 | 97.8 | ||||||||||
| Sound pressure level | Cooling | Nom. | dBA | 66 | 69 | 71 | 73 | 71 | 74 | 73 | 74 | 75 | 76 | 76.3 | 76.6 | 76.8 | 77.1 | 77.4 | ||||||||||
| Refrigerant | Type | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | R-32 | ||||||||||||
| Charge | kg | 12.7 | 15.8 | 18.5 | 26 | 34 | 34.8 | 43 | 41.7 | 48 | 47.1 | 48.6 | 60.3 | 70 | 78.5 | 80 | ||||||||||||
| Circuits | Quantity | 1 | 1 | 1 | 1 | 2 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | ||||||||||||
| Piping connections | Evaporator water inlet/outlet (OD) | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 88.9 | 114.3 | 114.3 | ||||||||||||
| Energy Efficiency Range | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | Space Heating A+++ ~ D, Water Heating A+ ~ F | |||||||||||||
| Power supply | Phase | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | ||||||||||||
| Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||||||||||||
| Voltage | V | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | 400 | ||||||||||||
| Voltage range | Min. | % | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | -10 | |||||||||||
| Max. | % | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | ||||||||||||
| Unit | Starting current | Max | A | 211.0 | 327.0 | 343.0 | 464.0 | 408.0 | 495.0 | 439.0 | 564.0 | 598.0 | 636.0 | 666.0 | 712.0 | 757.0 | 795.0 | 825.0 | ||||||||||
| Running current | Cooling | Nom. | A | 54.0 | 66.0 | 76.0 | 99.0 | 125.0 | 123.0 | 146.0 | 174.0 | 198.0 | 227.0 | 253.0 | 291.0 | 328.0 | 353.0 | 372.0 | ||||||||||
| Max | A | 68.0 | 85.0 | 101.0 | 131.0 | 166.0 | 163.0 | 197.0 | 232.0 | 266.0 | 304.0 | 334.0 | 379.0 | 425.0 | 463.0 | 493.0 | ||||||||||||
| Max unit current for wires sizing | A | 75.0 | 94.0 | 111.0 | 144.0 | 183.0 | 179.0 | 217.0 | 255.0 | 293.0 | 334.0 | 367.0 | 417.0 | 468.0 | 509.0 | 542.0 | ||||||||||||