FDQ125B8V3B9 |
FDQ200B8V3B9 |
FDQ250B8V3B9 |
Cooling capacity
|
Total capacity
|
Nom.
|
kW
|
|
20.0
|
24.1
|
Heating capacity
|
Total capacity
|
Nom.
|
kW
|
|
23.0
|
26.4
|
Casing
|
Colour
|
|
Unpainted
|
Unpainted
|
Unpainted
|
|
Material
|
|
Galvanised steel
|
Galvanised steel
|
Galvanised steel
|
Dimensions
|
Unit
|
Height
|
mm
|
350
|
450
|
450
|
|
|
Width
|
mm
|
1,400
|
1,400
|
1,400
|
|
|
Depth
|
mm
|
662
|
900
|
900
|
Weight
|
Unit
|
kg
|
59.0
|
89.0
|
94.0
|
Required ceiling void >
|
mm
|
350
|
450
|
450
|
Fan
|
Air flow rate
|
Cooling
|
Nom.
|
m³/min
|
43.0
|
|
|
|
Medium
|
m³/min
|
|
69.0
|
89.0
|
|
|
Heating
|
Nom.
|
m³/min
|
43.0
|
|
|
|
Medium
|
m³/min
|
|
69.0
|
89.0
|
|
External static pressure
|
High
|
Pa
|
150
|
250
|
250
|
|
|
Nom.
|
Pa
|
150
|
250
|
250
|
|
|
Low
|
Pa
|
150
|
250
|
250
|
Sound power level
|
Cooling
|
dBA
|
75.0
|
81.0
|
82.0
|
Sound pressure level
|
Cooling
|
High
|
dBA
|
44.0
|
45.0
|
47.0
|
|
Heating
|
Low
|
dBA
|
44.0
|
45.0
|
47.0
|
Piping connections
|
Liquid
|
OD
|
mm
|
9.52
|
9.52
|
12.70
|
|
Gas
|
OD
|
mm
|
15.9
|
22.2
|
22.2
|
|
Drain
|
|
|
OD Ø25.0
|
OD Ø25.0
|
Control systems
|
Wired remote control
|
|
|
BRC1D52, BRC1E52A/B
|
BRC1D52, BRC1E52A/B
|
Standard Accessories
|
Installation and operation manual
|
1
|
1
|
1
|
Power supply
|
Name
|
|
V3
|
V3
|
V3
|
|
Phase
|
|
1~
|
1~
|
1~
|
|
Frequency
|
Hz
|
50
|
50
|
50
|
|
Voltage
|
V
|
230
|
230 +/-10%
|
230 +/-10%
|
Notes
|
(1) - Sound values are measured in a semi-anechoic room with corrections.
|
(1) - Sound values are measured in a semi-anechoic room with corrections.
|
(1) - Sound values are measured in a semi-anechoic room with corrections.
|
|
(2) - The sound pressure level is measured via a microphone at 1m distance of the unit.
|
(2) - The sound pressure level is measured via a microphone at 1m distance of the unit.
|
(2) - The sound pressure level is measured via a microphone at 1m distance of the unit.
|
|
(3) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(3) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
(3) - Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
|
|
(4) - The sound power level is an absolute value indicating the power which a sound source generates.
|
(4) - The sound power level is an absolute value indicating the power which a sound source generates.
|
(4) - The sound power level is an absolute value indicating the power which a sound source generates.
|
|
(5) - For more details, please refer to wiring diagram, name plate and installation manual.
|
(5) - For more details, please refer to wiring diagram, name plate and installation manual.
|
(5) - For more details, please refer to wiring diagram, name plate and installation manual.
|