Specifications Table for FXFA-A

FXFA20A2VEB FXFA25A2VEB FXFA32A2VEB FXFA40A2VEB FXFA50A2VEB FXFA63A2VEB FXFA80A2VEB FXFA100AVEB (Preliminary) FXFA100A2VEB FXFA125A2VEB
Refrigerant Type                 R-32
  GWP                 675
Piping connections Liquid OD mm               9.52
  Gas OD mm               15.9
  Drain                 VP25 (O.D. 32 / I.D. 25)
Dimensions Unit Width mm               840
    Depth mm               840
    Height mm               246
Casing Material                 Galvanised steel plate
Weight Unit kg               24.0
Decoration panel 2 Model                 BYCQ140E2GFW1, BYCQ140E2GFW1B
  Dimensions Width mm               950
    Height mm               148
  Weight kg               10.3
  Dimensions Depth mm               950
Decoration panel 3 Model                 BYCQ140E2P, BYCQ140E2PB
  Dimensions Height mm               106
    Width mm               950
    Depth mm               950
  Weight kg               6.5
Decoration panel Weight kg               5.5
  Model                 BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B
  Dimensions Height mm               65
    Depth mm               950
    Width mm               950
Current - 50Hz Maximum fuse amps (MFA) A               16
Power supply Phase                 1~
  Frequency Hz               50/60
  Voltage V               220-240/220
Cooling capacity Total capacity At high fan speed kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0   11.2 14.0
Heating capacity Total capacity At high fan speed kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0   12.5 16.0
Power input - 50Hz Cooling At high fan speed kW 0.017 (1) 0.017 (1) 0.017 (1) 0.018 (1) 0.023 (1) 0.028 (1) 0.045 (1)   0.078 (1) 0.103 (1)
  Heating At high fan speed kW 0.017 (1) 0.017 (1) 0.017 (1) 0.018 (1) 0.023 (1) 0.028 (1) 0.045 (1)   0.078 (1) 0.103 (1)
Dimensions Unit Height mm 204 204 204 204 204 204 246   246 288
    Width mm 840 840 840 840 840 840 840   840 840
    Depth mm 840 840 840 840 840 840 840   840 840
Weight Unit kg 18 18 18 19 21 21 24   24 26
Casing Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate   Galvanised steel plate Galvanised steel plate
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 12.8 12.8 12.8 14.8 15.1 16.6 23.3   28.8 33.0
      At low fan speed m³/min 8.9 8.9 8.9 10.4 10.7 10.7 13.8   13.8 20.6
Refrigerant Type   R-32 R-32 R-32 R-32 R-32 R-32 R-32   R-32 R-32
  GWP   675 675 675 675 675 675 675   675 675
Sound power level Cooling At high fan speed dBA 49.0 49.0 49.0 51.0 51.0 53.0 55.0   60.0 61.0
Sound pressure level Cooling At high fan speed dBA 31.0 31.0 31.0 33.0 33.0 35.0 38.0   43.0 45.0
    At medium fan speed dBA 29.0 29.0 29.0 31.0 31.0 33.0 34.0   37.0 41.0
    At low fan speed dBA 28.0 28.0 28.0 29.0 29.0 30.0 30.0   30.0 36.0
  Heating At high fan speed dBA 31.0 31.0 31.0 33.0 33.0 35.0 38.0   43.0 45.0
    At medium fan speed dBA 29.0 29.0 29.0 31.0 31.0 33.0 34.0   37.0 41.0
    At low fan speed dBA 28.0 28.0 28.0 29.0 29.0 30.0 30.0   30.0 36.0
Piping connections Liquid Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection   Flare connection Flare connection
    OD mm 6 6 6 6 6 6 6   10 10
  Gas Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection   Flare connection Flare connection
    OD mm 9.52 9.52 9.52 12.7 12.7 12.7 12.7   15.9 15.9
  Drain   VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25)   VP25 (O.D. 32 / I.D. 25) VP25 (O.D. 32 / I.D. 25)
Decoration panel Model   BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B   BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B BYCQ140E2W1, BYCQ140E2W1W, BYCQ140E2W1B
  Dimensions Height mm 65 65 65 65 65 65 65   65 65
    Width mm 950 950 950 950 950 950 950   950 950
    Depth mm 950 950 950 950 950 950 950   950 950
  Weight kg 5.5 5.5 5.5 5.5 5.5 5.5 5.5   5.5 5.5
Decoration panel 2 Model   BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B   BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B
  Dimensions Height mm 148 148 148 148 148 148 148   148 148
    Width mm 950 950 950 950 950 950 950   950 950
    Depth mm 950 950 950 950 950 950 950   950 950
  Weight kg 10.3 10.3 10.3 10.3 10.3 10.3 10.3   10.3 10.3
Decoration panel 3 Model   BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB   BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB
  Dimensions Height mm 106 106 106 106 106 106 106   106 106
    Width mm 950 950 950 950 950 950 950   950 950
    Depth mm 950 950 950 950 950 950 950   950 950
  Weight kg 6.5 6.5 6.5 6.5 6.5 6.5 6.5   6.5 6.5
Air filter Type   Resin net Resin net Resin net Resin net Resin net Resin net Resin net   Resin net Resin net
Standard Accessories Washer for hanger bracket 8 8 8 8 8 8 8   8 8
  Wire clamp material 7 7 7 7 7 7 7   7 7
  Clamp for drain hose 1 1 1 1 1 1 1   1 1
  Clamps 1 1 1 1 1 1 1   1 1
  Drain hose 1 1 1 1 1 1 1   1 1
  Installation and operation manual 1 1 1 1 1 1 1   1 1
  Installation guide 1 1 1 1 1 1 1   1 1
  Insulation for fitting 2 2 2 2 2 2 2   2 2
  Screws 4 4 4 4 4 4 4   4 4
  Sealing pads 1 1 1 1 1 1 1   1 1
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~   1~ 1~
  Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60   50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220   220-240/220 220-240/220
Current - 50Hz Maximum fuse amps (MFA) A 6 6 6 6 6 6 6   6 6
Notes (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting.   (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting.