Specifications Table for VAM-FC

VAM150FCVE VAM250FCVE VAM350FCVE (Archived) VAM500FCVE (Archived) VAM650FCVE (Archived) VAM800FCVE (Archived) VAM1000FCVE (Archived) VAM1500FCVE (Archived) VAM2000FCVE (Archived)
Operation range Min. °CDB -15 -15 -15 -15 -15 -15 -15 -15 -15
  Max. °CDB 50 50 50 50 50 50 50 50 50
  Relative humidity % 80 or less 80 or less 80 or less 80 or less 80 or less 80 or less 80 or less 80 or less 80 or less
SEC class B, See note 4 B, See note 4
Weight Unit kg 24.0 24.0 33.0 33.0 51.0 54.0 63.0 128 145
Heat exchange system Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange
Operation mode Heat exchange mode, bypass mode, fresh-up mode Heat exchange mode, bypass mode, fresh-up mode Heat exchange mode, bypass mode, fresh-up mode Heat exchange mode, bypass mode, fresh-up mode Heat exchange mode, bypass mode, fresh-up mode Heat exchange mode, bypass mode, fresh-up mode Heat exchange mode, bypass mode, fresh-up mode Heat exchange mode, bypass mode, fresh-up mode Heat exchange mode, bypass mode, fresh-up mode
Maximum flow rate at 100 Pa ESP Flow rate m³/h 130 207
Sound power level (Lwa) dB 40 43 48 50 51 53 53 55 57
Annual electricity consumption kWh/a 771 (4) 580 (4)
Power input - 50Hz Heat exchange mode Nom. Ultra high kW 0.132 0.161 0.071 (1) 0.147 (1) 0.188 (1) 0.320 (1) 0.360 (1) 0.617 (1) 0.685 (1)
  Bypass mode Nom. Ultra high kW 0.132 0.161 0.071 (1) 0.147 (1) 0.188 (1) 0.320 (1) 0.360 (1) 0.617 (1) 0.685 (1)
Heat exchange element Specially processed non-flammable paper Specially processed non-flammable paper Specially processed non-flammable paper Specially processed non-flammable paper Specially processed non-flammable paper Specially processed non-flammable paper Specially processed non-flammable paper Specially processed non-flammable paper Specially processed non-flammable paper
Sound pressure level - 50Hz Heat exchange mode Ultra high dBA 27.0 28.0 32.0 33.0 34.5 36.0 36.0 39.5 40.0
  Bypass mode Ultra high dBA 27.0 28.0 32.0 33.5 34.5 36.0 36.0 40.5 40.0
Dimensions Unit Width mm 776 776 828 828 1,000 1,000 1,000 1,510 1,510
    Depth mm 525 525 816 816 868 868 1,160 868 1,160
    Height mm 285 285 301 301 364 364 364 726 726
Casing Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate
Fan External static pressure - 50Hz Ultra high Pa 90.0 70.0 103 (1) 83.0 (1) 100 (1) 109 (1) 147 (1) 116 (1) 132 (1)
  Air flow rate - 50Hz Heat exchange mode Ultra high m³/h 150 250 350 (1) 500 (1) 650 (1) 800 (1) 1,000 (1) 1,500 (1) 2,000 (1)
    Bypass mode Ultra high m³/h 150 250 350 (1) 500 (1) 650 (1) 800 (1) 1,000 (1) 1,500 (1) 2,000 (1)
Annual heating saved Cold climate kWh/a 8,941 (4) 8,426 (4)
  Average climate kWh/a 4,571 (4) 4,307 (4)
  Warm climate kWh/a 2,067 (4) 1,948 (4)
Connection duct diameter mm 100 150 150 200 200 250 250 350 350
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~
  Name   VE VE VE VE VE VE VE VE VE
  Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220
Notes (1) - Measured on fan curve 15. Refer to fan curves. (1) - Measured on fan curve 15. Refer to fan curves. (1) - Measured on fan curve 15. Refer to fan curves. (1) - Measured on fan curve 15. Refer to fan curves. (1) - Measured on fan curve 15. Refer to fan curves. (1) - Measured on fan curve 15. Refer to fan curves. (1) - Measured on fan curve 15. Refer to fan curves. (1) - Measured on fan curve 15. Refer to fan curves. (1) - Measured on fan curve 15. Refer to fan curves.
  (2) - Measured according to JIS B 8628 (2) - Measured according to JIS B 8628 (2) - Measured according to JIS B 8628 (2) - Measured according to JIS B 8628 (2) - Measured according to JIS B 8628 (2) - Measured according to JIS B 8628 (2) - Measured according to JIS B 8628 (2) - Measured according to JIS B 8628 (2) - Measured according to JIS B 8628
  (3) - Measured at reference flow rate according to EN13141-7 (3) - Measured at reference flow rate according to EN13141-7 (3) - Measured at reference flow rate according to EN13141-7 (3) - Measured at reference flow rate according to EN13141-7 (3) - Measured at reference flow rate according to EN13141-7 (3) - Measured at reference flow rate according to EN13141-7 (3) - Measured at reference flow rate according to EN13141-7 (3) - Measured at reference flow rate according to EN13141-7 (3) - Measured at reference flow rate according to EN13141-7
  (4) - In accordance with commission regulation (EU) No 1254/2014 (4) - In accordance with commission regulation (EU) No 1254/2014 (4) - In accordance with commission regulation (EU) No 1254/2014 (4) - In accordance with commission regulation (EU) No 1254/2014 (4) - In accordance with commission regulation (EU) No 1254/2014 (4) - In accordance with commission regulation (EU) No 1254/2014 (4) - In accordance with commission regulation (EU) No 1254/2014 (4) - In accordance with commission regulation (EU) No 1254/2014 (4) - In accordance with commission regulation (EU) No 1254/2014
  (5) - In accordance with commission regulation (EU) No 1253/2014 (5) - In accordance with commission regulation (EU) No 1253/2014 (5) - In accordance with commission regulation (EU) No 1253/2014 (5) - In accordance with commission regulation (EU) No 1253/2014 (5) - In accordance with commission regulation (EU) No 1253/2014 (5) - In accordance with commission regulation (EU) No 1253/2014 (5) - In accordance with commission regulation (EU) No 1253/2014 (5) - In accordance with commission regulation (EU) No 1253/2014 (5) - In accordance with commission regulation (EU) No 1253/2014
  (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014 (6) - At reference flow rate in accordance with commission regulation (EU) No 1254/2014
  (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency. (7) - Clean the filter when the filter icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and for the unit's energy efficiency.
  (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (8) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (9) - Maximum allowable voltage range variation between phases is 2%. (9) - Maximum allowable voltage range variation between phases is 2%. (9) - Maximum allowable voltage range variation between phases is 2%. (9) - Maximum allowable voltage range variation between phases is 2%. (9) - Maximum allowable voltage range variation between phases is 2%. (9) - Maximum allowable voltage range variation between phases is 2%. (9) - Maximum allowable voltage range variation between phases is 2%. (9) - Maximum allowable voltage range variation between phases is 2%. (9) - Maximum allowable voltage range variation between phases is 2%.
  (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000) (10) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2); MFA ≤ 4 x FLA; (VAM2000 is regarded as 2x VAM1000)
  (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA (11) - Select wire size based on the value of MCA